The New Conventional fire control panels offer state of the art architecture in configurations that deliver an uncomplicated solution for small to mid-sized conventional applications. With their clean and attractive contemporary design, they fits with any decor. The basic and intuitive user interface with icons make easy their application everywhere. With support for multiple lines of conventional detectors and accessories, these quick-to-configure systems offer versatility that benefits building owners and installation/maintenance companies alike.

The Panel

The NC-PX3 is a conventional fire alarm and extinguishing control panel. It is supplied in local language with 3 fire zones that support up to 32 devices per zone. These zones may be configured for extinguishing in single zone or double zone configuration in any combination of zones. In addition the panel offers supervised outputs for first stage notification, second stage notification as well as optical warning indicators and actuator activation. Standard relay outputs are provided for EN54 compliance and system status notification, as well as multiple inputs for system control.

Options

The panels support 2 types of auxiliary relay boards, one with 4 standard relays, and one with 4 supervised relays. With these boards the panel outputs may be expanded with up to 16 additional outputs.

Approvals & Compliance

The product line carries the following accreditations: • EN54:2, EN54:4 and CE approved • CPD certified • EN12094-1 certified • WEEE compliant • RoHS compliant

Key features:

  • Modern, elegant design with basic and intuitive user interface with icons.
  • Easy removable parts for quick and easy installation
  • Normal & head-out supervision support per zone
  • Three detection zones
  • Single zone, double zone or any combination of zones configurable for release
  • 6 Pre-configured relays and 8 supervised inputs for extinguishing control
  • Configurable fire routing, sounder, extinguishing, reset and door monitoring delays
  • Configurable "Hold Mode" type-A or type-B
  • Sounders configurable for pulsing or continuous operation
  • Extinguishing agent flow confirmation
  • Continuous or resetable 24 VDC auxiliary supply
  • Auxiliary standard & supervised relay output support
  • Default support for special functions such as: - EN54 compliant user access levels - Basic & Advanced level configuration - mixed zones - front panel diagnostics with test & disable control - one-man walk test

Technical specifications:

General
Maximum system capacity (device count)up to 96
Electrical
Power supply typeVAC
Power consumption4 A @ 24 VDC
Operating voltage110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)<br>Cable type: 3 x 1.5 mm² (live, neutral, earth)
Current consumption3.15 A @ 110/1.5 A @ 240 VAC<br>2.78 A (Alarm, no devices)<br>0.39 A (Quiescent, no devices)
Loop
Maximum loop capacity3
Zone
Maximum zone capacityup to 3
Operating voltage22 VDC (18 to 24 VDC)
Quantity of devices per zone20 max.
Rating65 mA (max. Load)
Cable rating40 ohm (max. rsistance), 500 nF (max. capacitance)
Standby battery
Capacity2 x 12 V, 12 Ah (SLA)
Physical
Form factorMedium
Physical dimensions440 x 480 x 140 mm (W x H x D)
Net weight3.9 kg (without battery)
Shipping weight6 kg
ColourGrey (RAL 7035)
Mounting typeSurface mount
Cable entriesØ 20 mm - 20 / 2 / 26 (top / bottom / rear)
Environmental
Operating temperature-5 to +50°C
Storage temperature-20 to +70°C
Relative humidity10 to 95% noncondensing
EnvironnementIndoor
IP ratingIP30
Regulatory
CompliancyCPD, RoHS, WEEE
CertificationEN12094-1, EN54-13, EN54-2, EN54-4
Supervised Inputs
6
UseMCP Start, MCP Hold, MCP Abort, Pressure Switch, Gas Flow, Door Monitor
Non Supervised Inputs
2
UseAuto/Manual mode, Remote Reset
Supervised Outputs
4
UseFire Sounders, Extinguishing Sounders, Optical Indications, Actuator
Notification2 x 500 mA @ 24 VDC
Visual indictors1 x 500 mA @ 24 VDC
Actuator1 x 1 A @ 24 VDC
Non Supervised Outputs
4
UseHold Mode, Abort Mode, Manual Mode, Release Indication
Specification6 x 2 A @ 30 V
Auxilliary Supply Output
Output voltage24 VDC (21 to 28 VDC)
Load (max)250 mA