Se rendre au contenu

Kidde KE-DT3101W-HAB - Excellence series intelligent addressable heat detector with isolator

https://www.mcdservices.be/web/image/product.template/1637625/image_1920?unique=8d6573f

87,46 € 87.46 EUR 87,46 €

87,46 €

Not Available For Sale

  • Couleur
  • Marque
  • Environnement
  • Type de détecteur
  • Système incendie

Cette combinaison n'existe pas.

Couleur: Blanc
Marque: Kidde
Environnement: Intérieur
Type de détecteur: Thermique
Système incendie: Adressable

Conditions générales
Garantie satisfait ou remboursé de 30 jours
Expédition : 2-3 jours ouvrables

General

The innovative Excellence range of intelligent addressable devices offers advanced features for reliability and peace of mind. Coupled with features for ease of installation and maintenance on new fire detection systems, it’s a perfect match for exceptional overall performance.

The DT3101W-HAB is a Kidde Excellence series, traffic white addressable heat detector with integrated short circuit isolation. It supports EN54 Class A with static and rate-of-rise temperature response, as well as Class B with rate-of-rise response. It combines a low profile design with tri-colour status indication with 360° visibility. A remote indicator output is available as standard that supports a remote indicator up to 30 m away.

User friendly

All detectors are individually identified by easily setting an address through 2, modern design rotary switches. The address is a directly identified number and does not require binary or hexadecimal conversions that significantly reduces the risk of incorrect addressing.

Installation & maintenance friendly

Regular automatic self-testing ensures safe operation with any issues immediately reported to the CIE.

All Excellence series detectors are compatible with a standard base which makes installation planning seamless and detectors easily interchangeable.

Communication protocol

An enhanced protocol ensures the overall integrity and error-free operation of the system. The Excellence series protocol provides features like CRC error checking and multiple bus cycle codes to ensure reliability between panel and device communication. The Kidde Excellence protocol still support legacy 2000 series devices in combination with the Kidde Excellence series devices.

Extended applications

A comprehensive range of additional devices and accessories complement every Excellence series device. Appart from a feature rich detector line, a comprehensive range of in- and outdoor manual call points as well as a variety of I/0 modules and accessories enrich the overall Excellence system capability.

Key features:

  • Integrated loop short circuit isolation ensures operation during a single short circuit on the loop
  • Short circuit isolation on remote output for additional device protection
  • Regular automatic self testing for operational piece of mind
  • Static and rate-of-rise temperature support
  • Tri-colour indicators for alarm, pre alarm, isolation, fault. ItsMe, and communications takes the guesswork out of operational status
  • 360° indicator visibility means no device alignment to ensure visibility
  • New mechanical rotary addressing for easy addressing
  • Event logging in the device for diagnostics purposes when needed
  • All alarm levels EN54 certified

Technical specifications:

General
Status indicationTri-colour LED
CompatibilitéKidde Commercial Excellence Systems
Alarm levels3
Event logAvailable
ConnectivitéExcellence series, standard base
Addressing methodRotary switch
Electrical
Power supply typeLoop powered
Operating voltage17 to 29 VDC
Communication voltage4 to 11 V pulsed
Current consumption4.75 mA (alarm at 24 VDC)<br>180 µA (quiescent at 24 VDC)
Terminals6
Detection
Detection principleStatic & temperature change
MonitoringAlarm threshold, Fault
SensitivitySelectable
Coverage area< 57 m²
Alarm temperature (minimum)+54°C
Rate-of-riseSupported
Installation height< 7.5 m (std) / < 9 m (reduced spacing & risk assessment)
Output
Output quantity1
Output type and ratingRemote indicator
ProgrammableNo
Remote alarm output<8 mA
Isolation
TypeNegative line break
Quantity per loop≤128
Isolation voltage14 to 15.5 VDC
Reconnect voltage14 to 15.5 VDC
Loop current5 mA (isolated)
Switch current1.05 A (continuous) / 1.4 A (pulsed)
Leakage current<1 mA
Series resistance<0.08 Ω
Impedance requirements≤32 devices between isolators
Physical
Physical dimensions100 x 54 mm (Ø x H)
Net weight110 g
ColourWhite (RAL 9016)
Mounting typeBase mount
Material (body)PC / ABS
Functional markingDevice type, Isolation
Environmental
Vandal proofNo
Operating temperature-10 to +65°C
Storage temperature-30 to +75°C
Application temperature (maximum)+65°C
Application temperature (typical)+25°C
Relative humidity10 to 93% noncondensing
EnvironnementIndoor
IP ratingIP20
Regulatory
CompliancyCE, REACH, RoHS 3, WEEE
CertificationCPR
StandardsEN54-5, EN54-17

Documentation : Fiche technique (FR) · Notice d'installation (FR) · Fiche technique (EN) · BIM 3D model (EN)