General

The innovative Excellence range of intelligent addressable devices offers advanced features for reliability and peace of mind. Coupled with features for ease of installation and maintenance on new fire detection systems, it’s a perfect match for exceptional overall performance.

The DP3121W-SNV is a Kidde Excellence series, traffic white addressable dual optical and heat detector with integrated short circuit isolation, sounder and VAD (Visual Alarm Device). It combines a low profile design with dual tri-colour status indication with 360° visibility. A remote indicator output is available to support a remote indicator up to 30 m away.

Detection reliability is ensured by combining dual optical wavelengths with multiple detection angles. This allows for state-of-the-art particle size detection that differentiates between real sources of alarm, or nuisance sources such as dust and steam. As a temperature detector, Class-A static and rate-of-rise modes are supported to further widen the application footprint.

Integrated notification

Every detector supports a freely programmable, audible and visual alarm device that can be independently controlled from the CIE. The sounder supports 32 alarm tones, each configurable at 4 alarm levels that allows complete customisation for the application and the alarm situation. The EN54-23 certified VAD offers 3 power ratings adding to full flexibility for management of loop loading on a system level.

User friendly

All detectors are individually identified by easily setting an address through 2, modern design rotary switches. The address is a directly identified number and does not require binary or hexadecimal conversions that significantly reduces the risk of incorrect addressing.

Installation & maintenance friendly

All Excellence series detectors are compatible with a standard base which makes installation planning seamless and detectors easily interchangeable. Self-testing and drift compensation ensure safe operation with contamination warnings provided when maintenance is needed.

Communication protocol

An enhanced protocol ensures the overall integrity and error-free operation of the system. The Excellence series protocol provides features like CRC error checking and multiple bus cycle codes to ensure reliability between panel and device communication. The Kidde Excellence protocol still support legacy 2000 series devices in combination with the Kidde Excellence series devices.

Key features:

  • Integrated loop short circuit isolation ensures operation during a loop overload
  • Short circuit isolation on remote indicator output for additional device protection
  • Nuisance alarm, steam & dust discrimination for superior false alarm immunity
  • Regular automatic self testing for operational piece of mind
  • Static and rate-of-rise temperature support
  • Tri-colour indicators for alarm, pre alarm, isolation, fault, ItsMe and communications takes the guesswork out of operational status
  • 360° indicator visibility means no device alignment to ensure visibility
  • Easy mechanical rotary addressing
  • Event logging in the device for advanced diagnostics purposes
  • Supports 32 multi-stage tones at 4 alarm levels up to 86 dB(A)
  • Supports visual alarm notification at 3 levels up to C-3-9

Technical specifications:

General
Status indicationTri-colour LED
CompatibilitéKidde Commercial Excellence Systems
Alarm levels5
Event logAvailable
ConnectivitéExcellence series, standard base
Addressing methodRotary switch
Electrical
Power supply typeLoop powered
Operating voltage17 to 29 VDC
Communication voltage4 to 11 V pulsed
Current consumption< 40 mA (alarm at 24 VDC - notification level dependant)<br>500 µA (quiescent at 24 VDC)
Terminals6
Detection
Detection principleOptical light scatter, forward and backward / Heat
MonitoringAlarm threshold, Contamination level, Fault
SensitivitySelectable
Coverage area< 57 m²
Particle sensitivity range0.1 to 0.25 dB/m ±20%
Alarm temperature (maximum)+70°C
Alarm temperature (minimum)+54°C
Rate-of-riseSupported
Installation height< 3 m
Heat class (per EN54)A2S / A2R
Test fires (to ISO 7240)TF1, TF2, TF3, TF4, TF5, TF8, TF9
Output
Output quantity1
Output type and ratingRemote indicator
ProgrammableNo
Remote alarm output<8 mA
Isolation
TypeNegative line break
Quantity per loop≤128
Isolation voltage14 to 15.5 VDC
Reconnect voltage14 to 15.5 VDC
Loop current5 mA (isolated)
Switch current1.05 A (continuous) / 1.4 A (pulsed)
Leakage current<1 mA
Series resistance<0.08 Ω
Impedance requirements≤32 devices between isolators
Physical
Physical dimensions100 x 54 mm (Ø x H)
Net weight205 g
ColourWhite (RAL 9016)
Mounting typeBase mount
Material (body)PC / ABS
Material (contacts)Brass
Functional markingDevice type, Isolation
Environmental
Vandal proofNo
Operating temperature-10 to +55°C
Storage temperature-30 to +75°C
Application temperature (maximum)+50°C
Application temperature (typical)+25°C
Relative humidity10 to 93% noncondensing
EnvironnementIndoor
IP ratingIP21C
Regulatory
CompliancyCE, REACH, RoHS 3, WEEE
CertificationCPR
Voluntary marksBOSEC
StandardsEN54-3, EN54-5, EN54-7, EN54-17, EN54-23
Sounder
Output level51 to 99 dB(A) - Tone dependent
Output level adjustment4 levels
FrequencyUser selectable
Selectable tones32
SynchronizationSupported
No. of stages3
VAD
ColourRed
RatingUser selectable up to C-3-9
Floor coverage< 40 m²
Flash frequency0.5 Hz (1 flash every 2 s)
SynchronizationSupported