Product overview
The KE-DM3100 Series is an intelligent range of addressable, Excellence Series manual call points with integrated isolation. The KE-DM3110R-KITF is a red, single action indoor MCP with a House-on-Fire functional indicator. It is delivered complete with back box, protection flip cover, resettable element, test connector and test key. Multiple optional accessories are available to facilitate most indoor installation requirements.
Aesthetics
This single action MCP is a standard profile, indoor MCP suitable for surface mount installations using standard back box. With its designer dual, tricolour LEDs it offers 180°, clear local indication of its operational status, even from a side view in a passage installation and with the flip cover installed. The clean face of the MCP is further enhanced by a front access & test key facility which is accessible without adjustment to the flip cover.
Installation & maintenance friendly
The front facing access for an aesthetically matching test key allows unhindered access regardless of the installation location. The MCP key doubles as a test and disassembly tool allowing removal of the MCP front cover without the need for additional tools.
Compatibility
The KE-DM3000 range may be used on all Kidde Excellence Series fire systems, and are also compatible with legacy Aritech fire systems. They can in many cases be deployed into existing systems without CIE configuration changes.
Key features: - Reliable single action manual call point for surface mounting
- Integrated short circuit isolation for added safety
- Dual, tri-colour status indicators offers 180° alarm visibility
- Tamper resistant design with resettable or optional frangible element
- Unobtrusive front facing test facility
- Standard mounting options facilitates easy retrofitting to existing installations
- Matching back box with rear, top and bottom cable entry
- Screen connection terminal in the back box for electrically noisy installations
- Pluggable connector with link through facility for ease of installation and pre-commissioning testing
- An alarm flag on the face of the manual call point allows alarm indication even without alarm LEDs
- Fast, no-tools-required maintenance using the test key
- Flip cover with breakable seal for protection against accidental activation
- Up to 128 devices supported per loop
|
Technical specifications: | General | | Status indication | Dual LEDs, Alarm (red constant), Isolated (yellow constant), Fault (yellow blinking), Communication (green blinking) | | User interface | LEDs, alarm flag | | Compatibilité | Excellence and legacy Aritech series fire systems | | Connectivité | 2-wire loop | | Addressing method | DIP Switches | | Electrical | | Power supply type | Loop powered | | Operating voltage | 17 to 29 VDC | | Communication voltage | 4 to 11 V pulsed | | Current consumption | 200 μA (quiescent)<br>2.8 mA (alarm) | | Cable specification | 0.404 to 2.05 mm (0.13 to 3.31 mm²) | | No. of cable cores | 2 | | Terminals | 4 (A+/A-;B+/B-) | | Detection | | Detection principle | Push button/switch | | Monitoring | Activated, Fault, Off, Short circuit | | Response time | < 3 s | | Installation height | Determined by local regulation | | Isolation | | Type | Negative line break | | Quantity per loop | ≤128 | | Isolation voltage | 14 to 15.5 VDC | | Reconnect voltage | 14 to 15.5 VDC | | Loop current | 1 A (Continuous) | | Switch current | 1 A (Pulsed) | | Leakage current | <1 mA | | Series resistance | <0.06 Ω | | Impedance requirements | <32 devices between isolators | | Physical | | Physical dimensions | 87 × 87 × 26 mm (without back box)<br>87 × 87× 57 mm (with back box)<br>109 x 94 x 81 mm (with back box & flip cover) | | Net weight | 110 g (without back box)<br>165 g (with back box)<br>225 g (with back box & flip cover) | | Colour | Red (RAL 3028) | | Mounting type | Back box, Wall mount | | Cable entries | 4 (3 side, 1 rear) | | Material (body) | Flame retardent ABS | | Functional marking | House on Fire | | Environmental | | Vandal proof | No | | Operating temperature | −25 to +72°C | | Storage temperature | −25 to +72°C | | Relative humidity | 10 to 95% noncondensing | | Environnement | Indoor | | IP rating | IP41 | | Regulatory | | Compliancy | CE, REACH, RoHS 3, WEEE | | Certification | CPR | | Standards | EN54:11, EN54:17 |
|
Documentation : Fiche technique (FR) · Notice d'installation (FR) · Fiche technique (EN)