General

The GBX2000 is a galvanic isolation barrier selected specifically for use between an Intrinsically safe conventional zone and a zone-monitor.

Application

Every GBX2000 (4 terminals) functions like a ""DC current isolator"" with reverse polarity protection. The input and output are galvanically isolated from each other. It is designed for the connection of fire detectors, smoke detectors, temperature sensors, etc. The detector's increased current range and the higher accuracy allow for differentiation between normal operation, fire alarm, lead breakage and short circuit currents in the safe area. In many cases they may also be used for controlling I/P converters. A separate power supply with auxiliary power is not required. Due to the input voltage limiting of 24 V, the maximum voltage output is 21 V.

Application

• The isolation of power loops for the control of positioner, I/P converters etc. A current source is connected to the safe area terminals. • The isolation of a current signal from fire detectors or similar sensors. In this case, a voltage source can be connected to the safe area terminals. A specific measurement current across a passive sensor can be measured in the safe area with a series resistor (min. 50 ¿). When a voltage supply is used, the measuring resistor can also provide current limitations.

Key features:

  • Approved with the IU2055 zone monitor unit
  • Output EEx ia IIC
  • Device installation permissible in zone 2
  • Polarity reversal protected
  • Accuracy 1%
  • EMC acc. to NAMUR NE 21
  • Up to SIL2 acc. to IEC 61508

Technical specifications:

Electrical
Operating voltage4 to 35 VDC
Physical
Physical dimensions20 x 107 x 115 mm
Net weight± 100 g
Mounting typeDIN-rail
Environmental
Operating temperature-20 to +60°C
EnvironnementIndoor, IS
IP ratingIP20
Regulatory
CertificationCENELEC/ATEX
Inputs/outputs (intrinsically safe)
Voltagefor 4 V < Uin < 24 V: ≥ Uin - (0.37 x current in mA) - 1.0 for Uin > 24 V: = 21 V - (0.36 x current in mA)
Short-circuit currentat Uin > 24 V: ≥ 65 mA
Transfer current≤ 40 mA
Current0 to 40 mA
Power lossat 40 mA and Uin < 22 V: 700 mW at 40 mA and Uin > 22V: 1.2 W
Group, category, type of protection
II (1) G D [EEx ia] IIC (-20°C ≤ Tamb ≤ 60°C)
Type of protection [EEx ia]
Explosion groupIIA IIB IIC
External capacitance2.9 µF 0.82 µF 0.107 µF
External inductance33 mH 18 mH 4.3 mH

Documentation : Fiche technique (FR) · Fiche technique (EN)