General

ModuLaser is a scalable aspirating smoke detection solution that makes installation easier, maintenance quicker, and takes applications further than traditional air sampling detectors. Two basic module types comprise the ModuLaser solution: a display module, and a detector module. Each detector module can accommodate up to 250 meters combined sampling pipe. Display modules and detector modules communicate by RS-485 interconnections.

Display modules are available in three configurations: Standard with TFT color display, status LED's and navigation buttons, Minimum with only status LED's, and Command which is similar to the Standard but with the added functionality to control various modules over SenseNET. The Minimum and Standard Display Modules can each support up to 8 detector modules, while the Command Display Module can support up to 127 modules across the SenseNET network.

Standard display module

The Standard Display Module features a user interface which consist of a TFT color display, navigation buttons and status LED’s. Configuration of the Standard Display Module (and associated detectors modules) can be done via the user interface, via a computer using Remote software or via SenseNET using a Command Display Module. The TFT color display support simple operations like changing configuration options via a menu driven structure, but also advanced features like viewing the chart recording in graphical format.

The Standard Display Module has two USB ports, one master and one slave. The master is used to connect a pen drive/memory stick, which in turn can be used for storing the configuration, the event logs or chart recordings, or for firmware upgrade purposes. While the USB slave is used to connect to a computer.

Perfect solution

Thanks to advanced features that make it virtually impervious to dust and dirt, ModuLaser is ideal for use in hostile environments that would disable other kinds of smoke detectors. Forward scattering optical detection adds early warning capability without the risk of nuisance alarms normally associated with high sensitivity smoke detection, while exclusive environmental compensation technology adds a high degree of reliability to an already solid detection solution.

Key features:

  • Modular Design : Separate centrally-controllable detector modules allow efficient piping and discrete zones with no overlap.
  • Zoned aspirating smoke detection : Individual detector modules provide detection for individual areas or zones, specific zone alarm information can be transmitted to the main fire alarm panel via a common APIC address card in the display module or through dedicated alarm relays within each detector module.
  • Simplified installation : Ingenious docking station design allows detectors to be easily connected together as a group. Sensitive electronics are easily removed to ensure they will not be damaged during first fix installation. Aspirating pipework and cable entries can easily be made into either the top or the bottom of the unit.
  • Intuitive user interface : Bright easy-to-see color TFT display and universal navigation and control buttons take the guesswork out of programming and diagnostics.
  • Easy pipe connection : The quick fit pipe adaptor system locks down securely, yet leaves plenty of room for easy pipe connection and removal.
  • Quick location of smoke : Each detector module is self-contained, which means no delays in determining in which zone (sampling pipe) smoke is present.

Technical specifications:

General
Status indicationLED's
User interfaceTFT and navigation buttons on Normal and Command Display Modules
Alarm levels4 (Aux, Pre-alarm, Alarm and Alarm 2)
Event log20 000 events per module
RS485 supportYes (SenseNET and SenseNET+)
ConnectivitéUSB (x2), IP and APIC on Display Module
Electrical
Operating voltage18 to 30 VDC
Current consumptionDisplay Module (at 24 VDC):<br> 204 mA - Minimum Display Module<br> 232 mA - Standard Display Module<br> 232 mA - Command Display Module<br>Detector Module (at 24 VDC):<br> 260 mA - fan speed 1<br> 380 mA - fan speed 6 (default speed)<br> 940 mA - fan speed 16
Detection
Detection principleLaser light scattering mass detection and particle evaluation
Particle sensitivity range0.003 to 10 microns
Sampling pipe
LengthUp to 250 m (820 ft.) combined per detector module
Quantity sampling holesUp to 20 - Class A per detector module<br>Up to 40 - Class B per detector module<br>Up to 50 - Class C per detector module
Inlet size27 or 25 mm (1.06 or 0.98 in) outer diameter
Inlet locationTop or bottom
Exhaust size27 or 25 mm (1.06 or 0.98 in) outer diameter
Exhaust locationTop or bottom
Inlet quantity1 per detector module
Input
Input quantity2 per module
Input type and ratingSupervised
Termination15 KΩ 5% 1/4 W
ProgrammableYes
Output
Output quantity3 per module
Output type and ratingVoltage free (contact rating 2 A at 30 VDC / NO/NC/C)
ProgrammableYes
Physical
Physical dimensionsW x D x H<br> 110.5 x 133.5 x 300 mm<br> (4.35 x 5.25 x 11.8 in)
Net weightDisplay Module:<br> 1.18 Kg (2.6 lb.)<br>Detector Module:<br> 1.57 Kg (3.46 lb.)
ColourGrey-white (RAL 9002)
Mounting typeSurface mount
Cable entries2 at the bottom, 2 at the rear, 2 at the top on Detector Module, and 3 at the top on the Display Module
Cable entry size20 mm (0.5 in) - top and bottom
Detector module orientationVertical (0 deg or 180 deg)
Environmental
Operating temperatureEquipment:<br>-10 to +60°C (14 to +140°F)<br>Sampled air:<br>-20 to +60 °C (-4 to +140 °F)
Relative humidity0 to 95% noncondensing
EnvironnementIndoor
IP ratingIP40
Regulatory
CompliancyREACH, RoHS
CertificationBOSEC, CPR, EN54-20
Chart recorder
Sampling periodAdjustable between 1s and 60 s
Capacity1 months @ 1s / Up to 5 years @ 60 s
Values recordedDetector value, 4 alarm level values, flow value and temperature (all simultaneously)

Documentation : Fiche technique (FR) · Manuel d'installation (FR) · Fiche technique (EN) · Compatibility list (EN) · BIM 3D model (EN) · Manuel d'installation (EN)