Aritech FD2705R - 2000 series addressable reflective beam detector 5 - 50m

https://www.mcdservices.be/web/image/product.template/1637929/image_1920?unique=e988dac

1.478,93 € 1478.93 EUR 1.478,93 €

1.478,93 €

Not Available For Sale

  • Couleur
  • Marque
  • Environnement
  • Type de détecteur
  • Système incendie

Cette combinaison n'existe pas.

Couleur: Noir
Marque: Aritech
Environnement: Intérieur
Type de détecteur: Linéaire (faisceau)
Système incendie: Adressable

Conditions générales
Garantie satisfait ou remboursé de 30 jours
Expédition : 2-3 jours ouvrables

General

The FD2705R and FD2710R provides an integral, loop powered analogue addressable reflective beam detector up to 100m distance.

Configuration

The FD2705R and FD2710R consist of an infrared transmitter and receiver in one single compact housing. The infrared signal is reflected by a prism and analysed for smoke presence. It is particularly designed to be use where point smoke detectors are not practical due to height or inaccessibility. The FD27xxR series units are loop powered for connection to 1200/2000 series fire panels. They use the Aritech 2000 series protocol.

Installer friendly

Wiring is restricted to a minimum as the transmitter and receiver are in the same housing. The detector is very easily aligned by means of checking the alignment LEDs. Easy alignment ensures optimum operation, both electrically and mechanically. The unit is easily tested using the graduated obscuration test card supplied. The low power consumption of the units allows multiple beams to be powered on the same loop without compromising the system's autonomy.

Reducing false alarms

Various alarm thresholds may be selected from to suit the environment. If the signal reduces to below the selected threshold and is present for ±10 seconds, a fire condition is signalled. If the infrared beam is obscured rapidly to a level of 90 % or greater for ±10 seconds, a fault condition is signalled. The detector monitors long term degradation of signal strength caused by component ageing or build up of dirt on optical surfaces.

Key features:

  • Loop Powered
  • Up to ceiling heights of 25 m
  • Low current consumption
  • 3 selectable alarm thresholds
  • Self check and automatic contamination compensation
  • Automatic discrimination between fire and fault
  • Vertical or horizontal mount
  • Easy wiring and unique alignment
  • Microprocessor controlled
  • Conforms to BS5839 part 5 and EN54

Technical specifications:

General
Status indicationLEDs
CompatibilitéAritech 2000 series systems
Alarm levels3
Connectivité2-wire loop
Addressing methodDIP Switches
Electrical
Power supply typeLoop powered
Operating voltage17 to 28 VDC
Current consumption5 mA (Quiescent)<br>14 mA (Alarm)<br>10 mA (Fault)<br>22 mA (Alignment mode)
Detection
Detection principleOptical light scatter
Coverage area<750 m²
Range5 to 50 m
Lateral detection7.5 m
Optical wave length880 nm
Installation height< 25 m
Misalignment toleranceDetector ± 0.4°, Prism ± 5.0° (@ 25%)
Physical
Physical dimensions130 x 210 x 120 mm( W x H x D)
Net weight770 g
ColourBlack, Grey
Mounting typeWall mount
Material (body)Flame retardent ABS
Environmental
Vandal proofNo
Operating temperature-10 to 55°C (32 to 100°F)
Relative humidity93% (non-condensing)
EnvironnementIndoor
IP ratingIP50
Regulatory
CompliancyCE, REACH, RoHS 3, WEEE
CertificationCPR
StandardsEN54:12