Se rendre au contenu

EMS FCX-532-001 - Fusion Wireless Interface Unit with Isolator

https://www.mcdservices.be/web/image/product.template/1637754/image_1920?unique=62a736f

868,21 € 868.21 EUR 868,21 €

868,21 €

Not Available For Sale

  • Marque
  • Environnement

Cette combinaison n'existe pas.

Marque: EMS
Environnement: Intérieur

Conditions générales
Garantie satisfait ou remboursé de 30 jours
Expédition : 2-3 jours ouvrables

General

The FCX-532-001 is an addressable zone monitoring unit for interfacing with a zone of wireless devices. It includes a loop short circuit isolator.

The FCX-532-001 acts as an interface between an intelligent control panel (CIE) and Fusion wireless field devices. It transfers the wireless data from the radio signal into the wired protocol both to and from the control panel, allowing the CIE to communicate seamlessly to these devices. The FCX-532-001 may be used on both the Aritech FP1200/2000 and well as the 2X fire panel ranges.

The Range

The Fusion series consists of: · Optical Smoke Detectors · Multisensor Smoke Detectors · A1R Heat Detectors · CS Heat Detectors · Sounders in red and white · Combination Sounder VIDs and VADs · Manual Call Points · Interface Modules

Operating Principle

Fire detection is often required in buildings where cabling presents a challenge because of the design or architecture of the building. Wireless installation provides the ideal solution to these environments.

Ideal for the application in hybrid systems where both wired and wireless devices share the same CIE. Multiple gateways can be incorporated on a single installation using an easy to use, site survey kit to confirm the positioning of the wireless devices. Every gateway supports up to 31 wireless devices.

Every Fusion wireless device is assigned an address which is recognised by the control panel in the same way as is the address of any wired device connected directly to the CIE loop wiring.

Key features:

  • Easy to install
  • Standard loop addressing
  • Self-monitoring
  • Eliminates cable installation problems
  • Uses European approved, 868MHz radio channels
  • Up to 31 devices per interface
  • Loop powered
  • On board, short circuit isolation

Technical specifications:

General
Status indicationLEDs
Wireless frequency868 MHz
CompatibilitéSystems with 900 Series protocol support
Electrical
Power supply typeExternal
Operating voltage17 to 28 VDC
Current consumption17 mA (typical)<br>91 mA (maximum)
Physical
Physical dimensions270 x 205 x 75 mm (w x h x d)
Net weight0.95 kg
Mounting typeCeiling mount, Wall mount
Environmental
Vandal proofNo
Operating temperature-10°C to 50°C
Storage temperature5°C to 30°C
Relative humidity< 95% non-condensing
EnvironnementIndoor
IP ratingIP54
Regulatory
CompliancyCE, REACH, RED (2014/53/EU), RoHS 2, WEEE
CertificationBOSEC, CPR
StandardsEN54-17, EN54-18, EN54-25<br>EN54-13

Documentation : Fiche technique (FR) · Manuel de configuration (FR) · Manuel d'installation (FR) · Fiche technique (EN) · Notice d'installation (EN) · Manuel de configuration (EN)