Se rendre au contenu

Aritech DT2063N-ISOKIT - ARITECH [10 pack], 2000 Series addressable heat detector with isolator base

https://www.mcdservices.be/web/image/product.template/1637931/image_1920?unique=48dc649

1.469,98 € 1469.98 EUR 1.469,98 €

1.469,98 €

Not Available For Sale

  • Marque
  • Environnement
  • Type de détecteur
  • Système incendie

Cette combinaison n'existe pas.

Marque: Aritech
Environnement: Intérieur
Type de détecteur: Thermique
Système incendie: Adressable

Conditions générales
Garantie satisfait ou remboursé de 30 jours
Expédition : 2-3 jours ouvrables

General

The DP2061N-ISOKIT pairs the popular 2000 series protocol addressable heat detector with an isolator base. The detector is certified to EN54 heat class A2 and includes a rate-of-rise algorithm that allows the device to raise the alarm before the fixed temperature trigger point is reached. Dual fire LEDs indicate an alarm visible from all directions, eliminating the need for special detector orientation on installation, whilst a remote indicator output is provided as standard on every device.

The short circuit isolator incorporated in the base protects the integrity of the addressable loop in the case of an overload or short-circuit on part of the loop.

Installation Friendly

The DT2063N is individually identified by setting an address through two rotary switches. The address is a straight numerical value and does not require binary or hexadecimal conversions, significantly reducing the risk of incorrect addressing.

For special applications, the fixed temperature trigger level of the DT2063N may be set at the CIE to accommodate higher activation temperatures.

Loop Isolation

The DB2016 isolator base senses and isolates overload and short circuit faults on a 2000 series fire detector loop. A yellow LED on the device indicates an isolation condition.

In the event of a single short circuit, the detector connected to the DB2016 continues to operate normally. The the entire loop circuit is not lost as only the effected part of the loop between two isolators are removed (isolated) from the circuit.

State of the Art Communication

Panel to device communication is provided through a powerful SIA protocol featuring multiple bus cycle codes and CRC error checking and ensuring reliable communications between the device and the control panel. This enhanced protocol ensures the overall integrity and error free operation of the full system, without compromising speed.

Key features:

  • Dual thermistor heat detector with isolator
  • Remote signaling capabilities
  • Easy numeric addressing (1-128)
  • Enhanced communication protocol
  • Full diagnostic self testing
  • EN54:5 and EN54:17 approved and CPR certified

Technical specifications:

General
Status indicationDual red alarm LED, isolated yellow LED
User interfaceLED's
CompatibilitéAritech 2000 series systems
Alarm levels5
Connectivité2000 Series bases
Addressing methodRotary switch
Electrical
Power supply typeLoop powered
Operating voltage17 to 28 VDC
Current consumption< 300 µA (quiescent at 24 VDC)<br>4.7 mA (alarm at 24 VDC)<br>< 2 mA (isolated)
No. of cable cores2
Terminals5
Detection
Detection principleHeat
MonitoringAlarm threshold, Short circuit
SensitivityConfigurable
Coverage area<80 m²
Air velocityUnaffected
Alarm temperature (typical)> +40°C
Rate-of-riseClass A2
Output
Output quantity1
Output type and ratingRemote indicator
ProgrammableNo
Remote alarm output4.7 mA
Isolation
TypeNegative line break
Isolation voltage14 V
Reconnect voltage14.5 V
Switch current800 mA (max)
Series resistance0.1Ω
Physical
Physical dimensions101 x 63.5 mm (Ø x H)
Net weight132 g
ColourCloud white (RAL 9001)
Mounting typeCeiling mount
Cable entries1
Material (body)Plastic
Environmental
Vandal proofNo
Operating temperature−10 to +50ºC
Storage temperature-10 to +70°C
Application temperature (typical)+25°C
Relative humidity10 to 95% non-condensing
EnvironnementIndoor
IP ratingIP20
Regulatory
CompliancyCE, REACH, RoHS 3, WEEE
CertificationCPR
StandardsEN54-5, EN54-17

Documentation : Fiche technique (FR) · Notice d'installation (FR) · Notice d'installation (FR) · Fiche technique (EN)