Se rendre au contenu

Aritech DP721RTA - Détecteur de fumée photoélectrique et de chaleur avec sortie relais, réarmement automatique 12 volts

https://www.mcdservices.be/web/image/product.template/354897/image_1920?unique=48dc649

DP721RTA

111,80 € 111.8 EUR 111,80 €

111,80 €

Not Available For Sale

  • Marque
  • Environnement
  • Type de détecteur
  • Système incendie

Cette combinaison n'existe pas.

Marque: Aritech
Environnement: Intérieur
Type de détecteur: Multicapteur
Système incendie: Conventionnel

Conditions générales
Garantie satisfait ou remboursé de 30 jours
Expédition : 2-3 jours ouvrables

Preventing false alarms with self diagnostics

All Aritech 700 series smoke detectors continuously monitor their sensitivity and operational status. Background drift is daily compensated to maintain the original calibrated sensitivity within the required limits. Once a day the detector performs a full diagnostic test that includes dynamically testing the sensing chamber and internal electronics. If a detector drifts out of sensitivity range or fails the internal diagnostics test, this is reported back to the panel and indicated on the detector with a yellow fault LED.

Maintenance friendly sensitivity level test mode

The 700 Series photoelectric detectors include a sensitivity test mode that may be activated by simply holding a magnet near the detector's test point. This initiates a self-diagnostic routine and provides visual indication if service is required. This test mode allows field sensitivity testing without the requirement for external meters or test gas.

Field cleaning and service

The photoelectric sensing chamber unclips from the detector for easy field cleaning and service. During regular maintenance the detector cover can be removed, the optical chamber removed and replaced by a low cost, new chamber. On power up the detector auto-calibrates and returns to normal operating mode without any further intervention.

The right detector for the right job

For a truly fast and broad-spectrum detection the DP721RTA offers both optical and heat sensors. The interaction of both the smoke and heat algorithms ensure a quick response to both flaming and smouldering fires. All bases are provided with an integral locking tab for extra security if required. Bases are equipped with a shorting bar between IN and OUT that opens when the head is installed and that may be manually restored when removing the head. This simplifies cable continuity testing.

Note

The DP721RTA must not be used in applications requiring compliance with commercial or residential fire standards such as EN54-5/EN54-7/EN54-29/CEA4021/EN14604. Always ensure compliance with local codes and standards.

Key features:

  • Automatic self diagnostics with dynamic full detector and sensitivity test
  • High false alarm immunity with floating background with drift compensation
  • Separate fire and fault LEDs for unambiguous alarm reporting
  • Wide operating voltage for use on most conventional systems
  • Polarity insensitive for carefree installation
  • Manual self diagnostic with visual sensitivity indication
  • Field exchangeable and disposable optical chamber
  • Automatic reset when event clears
  • COM/NO/NC contacts for easy supervision on any system

Technical specifications:

General
Status indicationWhite LED (red in alarm), Yellow LED (test & fault)
User interfaceLEDs
CompatibilitéAritech conventional zones
Reset voltage<2.5 V
Reset time1 s
Alarm levels1
Connectivité700 Series conventional base
Electrical
Power supply typeZone powered
Operating voltage8.5 to 33 VDC
Current consumption100 µA (quiescent)<br><60 mA (in alarm)
Detection
Detection principleOptical light scatter and heat
MonitoringAlarm threshold, Contamination level
Sensitivity10%/m (+1.6%, -3.3%)
Zone length< 2 km (Cable dependent)
Rate-of-rise8°C/min above 40°C, Class A2
Output
Output quantity1
Output type and ratingRelay - NO/C/NC (1 A at 30 VDC, 0.5 A at 120 VAC)
ProgrammableNo
Remote alarm outputNo
Physical
Physical dimensions100 x 50 mm (Ø x H)
Net weight112 g
ColourCloud white (RAL 9001)
Mounting typeBase mount, Ceiling mount
Material (body)Plastic
Environmental
Vandal proofNo
Operating temperature-10 to +60°C
Storage temperature-10 to +70°C
Application temperature (typical)+25°C
Relative humidity0 to 95% noncondensing
EnvironnementIndoor
IP ratingIP43
Regulatory
CompliancyCE, REACH, RoHS 3, WEEE
CertificationCE

Documentation : Fiche technique (FR) · Fiche technique (EN) · Notice d'installation (EN)