Se rendre au contenu

Apollo DB952IAS - 950 Series Integrated Base Sounder With Isolator

https://www.mcdservices.be/web/image/product.template/1637945/image_1920?unique=1afdb35

232,88 € 232.88 EUR 232,88 €

232,88 €

Not Available For Sale

  • Marque
  • Environnement
  • Type de détecteur

Cette combinaison n'existe pas.

Marque: Apollo
Environnement: Intérieur
Type de détecteur: Socle & accessoire

Conditions générales
Garantie satisfait ou remboursé de 30 jours
Expédition : 2-3 jours ouvrables

General

The DB952IAS is a range of integrated, self monitoring base sounders with integral short-circuit isolator for use on Series 950 and Series 990 systems. They incorporate a base into which a series 950 or 990 detector, or beacon can be fitted. It may also be used with a red (AS952CAP-R) or white (AS952CAP-W) cap for stand-alone use.

Tones

The DB952IAS sounders support multiple tones. A low tone range is useful in areas such as hospitals where a fire alert is initially intended to warn staff only. The sounder may be set to the high range for general use. In addition to the standard tones in the DB952IAS, a slow whoop tone to Dutch standard NEN2575 is available in the DB952IAS-NEN, as well as a German standard DIN tone version in the DB952IAS-DIN.

Syncronisation

Synchronisation of tones ensures the integrity of the signal—tones from different sounders do not merge into one signal that could be mistaken for a different tone. DB952IAS sounders are synchronised with each other in both ‘alert’ and ‘evacuate’ modes.

Self Test

The acoustic self-test means that the sounder listens to itself when it is switched on. If no sound is detected a fault signal is transmitted when the sounder is polled. The same self-test feature may also be used during commissioning or periodical maintenance testing. The sounder may simply be activated for at least 5 seconds and the control panel checked for a fault signal. If none is received, the sounder is working properly.

Key features:

  • Two tone ranges 55 to 75 dB and 75 to 91 dB
  • Synchronisation of ‘alert’ and ‘evacuate’ tones
  • Individual sounder addressing
  • Available with built-in isolator
  • Acoustic self-test
  • Slow whoop option available

Technical specifications:

Electrical
Operating voltage17 to 28 VDC<br>5 to 9 V (Protocol pulses)
Current consumption5 mA @ 24 V (Sounder operated 75 - 91dB)<br>5 mA @ 24 V (Sounder operated 50 - 75 dB)<br>1.2 mA @ 24 V (Switch-on surge, <1 s)<br>200 μA @ 24 V (Quiescent)
Environmental
Operating temperature-20 to +60°C
Relative humidity0 to 95% noncondensing
EnvironnementIndoor
IP ratingIP21D
Regulatory
CertificationEN54-17, EN54-3
Sound output
Maximum at 90°91 dB(A)
Maximum to EN5483 dB(A)
Sound pressure levelTone dependent

Documentation : Fiche technique (FR) · Fiche technique (EN)