Overview

The new 2X-A series life safety control systems bring the speed and functionality of high-end intelligent processing to small to mid-sized addressable applications. Based on 2X series learned experience and with complete backwards compatibility, the new 2X-A features an attractive contemporary design that fits with any decor. With improved robustness, manufactured in metal, special plastics and easy electronics removal, it allows painting in any colour. The main controls are easily located using an improved and robust jog dial.

With high power loop addressable detection, a full line of easily configured option cards and modules, as well as USB and Ethernet® connectivity, these quick-to configure systems offer versatility that benefits building owners and life safety system installers alike.

This version of 2X-A panels includes a 7 inches touchscreen improving the user experience thanks to the more intuitive user interface.

The Panel

The fire panels supplied in local language, with user interface, with fire routing controls, with 2 High Power Loops that supports up to 256 devices in 512 zones, with 10A PSU, have standard 4 supervised sounder/fire-routing outputs, which can be used as freely programmable outputs as well. In addition 2 conventional relay outputs and 2 supervised outputs, working in pair and dedicated to common fire and fault conditions, as well as 2 user configurable inputs for monitoring and control are available.

Options

The panel supports an extra 2 High Power Loop board that brings the panel to up to 512 devices with 4 additional programmable outputs. Add a network board to create a maximum of 64 nodes / 256 loops network of fire panels and fire panel repeaters (including conventional fire panels and fire repeater panels up to a maximum of 64 conventional zones). Last but not least, in case seperate zone indications are required, a 20 or a 40 zone fire/fault LED indicator board can be mounted in the panel or repeater with ample space for custom text.

High loop power PAK available to increase the loop power from 500 mA to 800 mA.

Compatible with existing loop devices and network compatible with existing panels, repeaters (existing and new) and conventional panels.

Key features:

  • 2 High Power Loops expandable to 4 with 500 mA per loop
  • 7" touchscreen
  • High loop power PAK to increase the loop power from 500 mA to 800 mA
  • Up to 512 zones with Fire Brigade & Fire Protection controls and 300 output groups
  • Up to 40 LED Zone indicators for Fire and Fault with ample text space
  • Auto configuration, setup wizards and default regional setup modes
  • Ethernet port with TCP/IP for remote diagnostics, maintenance and programming
  • EN54 compliant graphical LCD with icons and up to 256 zones
  • Improved Jog Dial with 4 soft buttons for simple and intuitive user control
  • Aesthetic pleasing design with robust painted steel door
  • Easy removable door and chassis for quick and clean installation
  • All pluggable connectors
  • Up to 72 hours standby time and 30 minutes alarm
  • Auxiliary 24 VDC supply output with reset support
  • 3 USB ports with memory stick support and RS232 for printer support
  • Communication via UltraSync cloud, using EN 54-21 UC240 UltraSync communicator
  • Integration in management software ATS8600, allowing integration with security systems and CMS
  • 3 operator level menu structure (20 usernames and passwords)
  • Email notification for events directly from the panel (4 user accounts)
  • History log memory for 9999 events
  • Backwards compatible, supporting site retrofit/upgrades, expansions, replacement
  • Compatible with the new loop powered sounders/beacons and base sounders and the 2000 series detectors with replaceable optical chamber
  • Bigger power supply with 10A

Technical specifications:

General
User interfaceWith fire brigade controls
Maximum system capacity (device count)up to 32512
Network size (nodes)up to 64
Electrical
Power supply typeVAC
Operating voltage110 / 240 VAC (+10%/-15%)<br>Mains supply cable type: 3 x 1.5 mm² (live, neutral, earth)
Current consumptionNom. 0.6 / 1.3 A, Max. 1.5 A / 3.15 A
Loop
Maximum loop capacity4
Type and rating500 mA expandable to 800 mA at 37 VDC (28 to 37 VDC)
Cable ratingRecommended 2 core 1.5 mm² twisted pair ; 52 ohm / 500 nF ; max. 2 km
Zone
Maximum zone capacityup to 512
Input
Input quantity2
Input type and ratingSupervised, maximum moad 150 mA
Programmable2
Termination15 kohm
Output
Fire alarm signalling350 mA / 21 to 28 VDC (24 VDC nominal)
Fault signalling350 mA / 21 to 28 VDC (24 VDC nominal)
Notification8 sounder outputs
Supervisory voltageSupervised, 4,​ 750 mA / 21 to 28 VDC (24 VDC nominal)
Auxilliary power1 resetable, 500 mA / 21 to 28 VDC (24 VDC nominal)
ProgrammableUp to 8 (2 per loop board) / 21 to 28 VDC (24 VDC nominal)
Termination15 kohm
Standby battery
CapacityMax. 2 x 12 V / 18 Ah (use supplied cables)
Charging27.3 V at 20ºC ; 36 mV/ºC
Low battery warning threshold23.6 VDC ± 1% at 25ºC
Batteries supported in housingMax. 2 x 12 V / 18 Ah (use supplied cables)
Physical
Form factorLarge
Physical dimensions446 x 536 x 164 mm (W x H x D)
Net weight10.7 kg (without battery)
Shipping weight13.4 kg
ColourWhite (RAL 9003)
Mounting typeSurface mount
Cable entries18 (20 mm) / 2 (20 mm) / 2 removable plates (top / bottom / back)
MaterialSteel (painted)
Environmental
Operating temperature-5 to +40°C
Storage temperature-20 to +50°C
Relative humidity10 to 95% noncondensing
EnvironnementIndoor
IP ratingIP30, indoor use only
Regulatory
CompliancyCE, REACH, RoHS 3, WEEE
CertificationAEAI, BOSEC, CPR
StandardsEN54-2, EN54-4, EN54-13, EN54-21
Additional ApprovalDBI

Documentation : Fiche technique (FR) · Fiche technique (EN) · Quick installation guide (EN) · Manuel d'installation (EN) · Compatibility list (EN) · Compatibility list (EN) · BIM 3D model (EN) · Marketplace manual (EN)