Pular para o conteúdo

ffe FIREBEAMXTRA - FireBeam conventional beam detector with low level controller

https://www.mcdservices.be/web/image/product.template/1637793/image_1920?unique=38c3257

989,17 € 989.17 EUR 989,17 €

989,17 €

Not Available For Sale

  • Marque
  • Environnement
  • Type de détecteur
  • Système incendie

Essa combinação não existe.

Marque: ffe
Environnement: Intérieur
Type de détecteur: Thermique
Système incendie: Conventionnel

Termos e Condições
Garantia de devolução do dinheiro em 30 dias
Envio: 2-3 dias úteis

The Fire Beam XTRA is a conventional beam detector with a separate controller to facilitate the maintenance and operations. With its self-aligning motorised technology a range up to 160 meters on a reflective technology can be covered with the full extension kit installed./

Range extension

The FirebeamXTRA is supplied as a head unit with a low level controller, one reflector, short range mask (for distances under 20 m), a 3 mm allen key and quick start installation guide. This enables coverage distances up to 70 metres.

For distances between 70 to 140 metres an optional mid range extension kit is available. This kit is supplied with a backing plate and 3 extra reflectors.

For distances between 140 to 160 metres an optional long range extension kit is available. This kit is supplied with a backing plate and 8 extra reflectors.

Key features:

  • Standard detection range of 7 to 70 metres suitable for most installations
  • Extended range support up to 160 m using optional extender kits
  • Revised optics with market leading features
  • Faster commissioning and routine maintenance due to faster alignment motors
  • Auto-alignment ON/OFF section for full flexibility in theater environments
  • Auto-align time delay for environments that are liable to occasional short term obscuration
  • Beam phasing allows beams to face each other without interference
  • Hysteresis control allows a change the delay in returning from a fire state back to a normal state, avoiding successive alarms on auto-reset.

Technical specifications:

General
Status indicationLEDs and LCD diplay
User interfaceGround level controller
CompatibilityAll conventional fire detection systems
Reset voltage0 VDC
Reset time> 5 s
Alarm levels4
ConnectivityRelays and Controller
Electrical
Power supply typeVDC
Operating voltage10.2 to 30 VDC
Current consumption3.5 mA (all operational states)<br>17 mA (fast commissioning)
Detection
Detection principleOptical light scatter
MonitoringContinuously self-checking
SensitivityAdjustable (25% (1.25dB) to 50% (3dB) in 1% (0.05dB) increments - default 35% (1.87dB))
Coverage areaCountry dependant
Range7 to 70 m
Adjustment angle± 5°
Misalignment toleranceBeam Head ± 0.75° Reflector ± 2°
Optical wave length (all languages)870 nm
Response time (all languages)Adjustable (2 to 30 s in 1 s increments - default 10 s)
Fault sensitivity level< 4%
Output
Output quantity2
Output type and ratingChange over relays (Alarm & Fault - 2A @ 30 VDC)
Physical
Physical dimensions180 x 155 x 137 mm (H x W x D) - Head<br>185 x 120 x 62 mm (H x W x D) - Controller
Net weight1.1 kg - Head<br>0.55 kg - Controller
Mounting typeWall bracket, Wall mount
Environmental
Vandal proofNo
Operating temperature-10°C to +55°C
Relative humidity10 to 95% (Non-condensing)
EnvironmentIndoor
IP rating< IP65
Regulatory
CompliancyCE, REACH, RoHS 3, WEEE
CertificationCPR
Voluntary marksVdS
StandardsEN54-12
SKU Info
Product brand (all languages)thefirebeam™

Documentation: Fiche technique (FR) · Fiche technique (EN)