Skip to Content

Kidde NC-DBR-W - Conventional relay base (White)

https://www.mcdservices.be/web/image/product.template/1637490/image_1920?unique=2d2c67f

38,82 € 38.82 EUR 38,82 €

38,82 €

Not Available For Sale

  • Couleur
  • Marque
  • Environnement
  • Type de détecteur
  • Système incendie

This combination does not exist.

Couleur: Blanc
Marque: Kidde
Environnement: Intérieur
Type de détecteur: Socle & accessoire
Système incendie: Conventionnel

Termos e Condições
30-day money-back guarantee
Shipping: 2-3 Business Days

General

The NC-DBR-W is an NC series surface mount first-fix relay base offering one change over relay. It allows any NC Series conventional point detector to be inserted, removed or replaced without rewiring using an easy twist and lock action. The added potential free relay function allows for low cost control to non-critical functions such as door release, air conditioning shutdown or elevator control without the need for additional device installation. The status of the relay is associated with the alarm situation of the associated detector.

Ease of Installation

Forming an integral part of the detector assembly, NC Series standard bases are provided with key-hole slots for screw fixing direct to ceiling structures or conduit boxes. Large rear cable entry allows for easy wiring to the base.

For special applications a base accessory is available for surface installations, ensuring an easy and practical installation.

Ease of Wiring & Testing

Clearly marked terminals ensure correct and secure wiring termination for zone and relay connections.

Ease of Use

Inserting the NC Series detector into the base is accomplished with a simple turn and lock mechanism. To prevent unauthorised removal of a detector from its base, an easy-to-activate locking mechanism is incorporated into all NC series detectors. If activated, a detector can only be released from its base using a dedicated tool.

Key features:

  • Common first-fix mounting base for all white NC-Series detectors
  • Single potential free contacts for easy external function control
  • A selectable detector locking mechanism protects against unauthorised removal
  • Large rear cable entry with ample space for cables
  • Flexible installation fixture with first fix screw feature reduces installation time and effort
  • Clearly visible terminal marking avoids incorrect cabling
  • Robust, wiring terminals for easy installation
  • Simple twist-and-lock detector action ensures the detector is properly inserted
  • Dual contact points on every connector for reliable detector/base contact

Technical specifications:

General
CompatibilityNC-Series point detectors
Reset voltage< 1 VDC
Reset timeLinked to detector
Connectivity2-wire zone and NO/COM/NC contacts
Electrical
Power supply typeZone powered
Operating voltage9.5 to 28 VDC (24 VDC typical)
Current consumptionExcluding detector<br>≤10uA (standby)<br>≤10mA @ 9.5 VDC (active)
Cable specification1.0 to 2.1 mm² (17 to 14 AWG) shielded or unshielded twisted-pair
No. of cable cores2 for zone
Terminals7 used (3 Zone in/out + COM, NO, NC)
Output
Output quantity1
Output type and ratingSingle pole, change over, 1 A @ 30 VDC / 0.3 @ 125 VAC (resistive)
Physical
Physical dimensions100 x 21.3 mm (Ø x H)
Net weight70.1 g
ColourWhite (RAL 9016)
Mounting typeCeiling mount
Cable entries1
Material (body)ABS
Fixing centres2 (45 to 75 mm)
Material (contacts)QSn6.5-0.1 (Tin-phosphor bronze)
Environmental
Vandal proofNo
Operating temperature−20 to +65°C
Storage temperature−30 to +75°C
Relative humidity10 to 93% (noncondensing)
EnvironmentIndoor
IP ratingIP3x
Regulatory
CompliancyCE, REACH, RoHS 3, WEEE
CertificationCPR
StandardsEN54-18

Documentation: Fiche technique (FR) · Notice d'installation (FR) · Fiche technique (EN)